10. LCD Setting and Display
Setting Program: This setting is only available when the inverter is in standby mode (Switch
off).
Program
Description
Selectable option
28
AC output
mode
Single:
When the units are used in parallel
with single phase, please select PAL
in program 28.
Operation to support three-phase
equipment is required to have three
inverters. This setting for each unit
should be different in L1 phase, L2
phase and L3 phase separately. Please
set up this setting corresponding to
each phase connection.
No matter its set for parallel operation
or supporting 3-phase equipment, the
output source priority only can be set
as Utility or SBU. Besides, power
saving function will be automatically
disabled.
Parallel:
L1 phase:
L2 phase:
L3 phase:
Fault code display:
Fault Code
Fault Event
Icon on
60
Power feedback protection
71
Firmware version inconsistent
72
Current sharing fault
80
CAN fault
81
Host loss
82
Synchronization loss
83
Battery voltage detected different